4.5 Basic safety rules
• The product must be used by adults;
• Do not open or disassemble the product when it is electrically
powered;
• Do not touch the product if barefoot or with wet or damp parts
of the body;
• Do not pour or spray water on the product;
• Do not climb, sit and/or place any type of object on the prod-
uct.
4.6 Information on the refrigerant used
This product contains fluorinated greenhouse gases included in
the Kyoto protocol. Do not release these gases into the atmo-
sphere.
Type of refrigerant: HFC-R134a.
NB!: Maintenance and disposal operations must only be
carried out by qualified personnel.
5. INSTALLATION AND CONNECTIONS
ATTENTION! Product installation, commission-
ing and maintenance must be carried out by
qualified and authorized personnel. Do not try to
install the product yourself.
5.1 Preparation of place of installation
The product must be installed in a suitable place, i.e. to allow
normal use and adjustment operations as well as routine and
extraordinary maintenance.
The necessary operating space must therefore be prepared by
referring to the dimensions given in fig. 9.
200 mm
fig. 8 - Minimum spaces
The room must also be:
• Equipped with adequate water and electricity supply lines;
• Prearranged for the condensation water discharge connec-
tion;
• Prearranged with adequate water drains in case of boiler
damage or safety valve intervention or the breakage of pipes/
connections;
• Equipped with possible containment systems in case of seri-
ous water leakage;
• Sufficiently illuminated (where required);
• Not less than 20 m3 in volume;
• Protected against frost and be dry.
ATTENTION! To avoid the propagation of me-
chanical vibrations, do not install the equipment
on floors with wooden beams (e.g. in the attic).
cod. 3541T590 - Rev. 04 - 05/2020
300 mm
600 mm
fig. 9 - Minimum spaces
600 mm
77
EN