temperature maxi-
mum limitation
207 D.h.w. storage tank
temperature maxi-
mum limitation
208 Collector start func-
tion gradient
Final work
Locking the settings for district heat
The settings made for district heat can be locked by linking terminals "H3" and "M".
Then, if required, seal the fixing screw at the bottom: Insert plug (attached to the key ring) in
the screw hole; introduce a wire through both lugs and seal.
Completing the installation work
1. Enter the settings made in these Installation Instructions, which should be kept in a safe
place.
Building Technologies
(8...100)
°C
...................
90 °C
°C
(8...100)
...................
--- min/°C
min/°
(--- / 1...20)
...........
C
74 319 0618 0 a
No safety function
Setting --- = Function deacti-
vated
17.04.2008