68
Maximum optimum
shutdown
69
Maximum limitation
of room tempera-
ture
70
Effect of room
temperature
71
Boost of room
temperature set-
point with boost
heating
72
Parallel displace-
ment of heating
curve
73
Type of heating
curve adjustment
Block "3-position actuator for heating circuit"
81
Maximum limitation
of flow temperature
82
Minimum limitation of
flow temperature
Building Technologies
0:00 h
(0:00...6:00)
......................
h
--.- °C
(--.- / 0...35)
...................
4
(0...20)
........................
.
5 °C
(0...20)
...................
0.0 °C
(−4.5...+4.5)
...................
0
(0...2)
........................
.
--- °C
(--- / 0...140)
...................
--- °C
(--- / 0...140)
...................
74 319 0618 0 a
Maximum forward shift for
switching off before occu-
pancy ends
Setting 0:00 = no optimum stop
control
Setting --.- = limitation deacti-
vated
°C
Function only possible with
room unit / room temperature
sensor
Gain factor for effect of room
temperature
Function only possible with
room unit / room temperature
sensor
°C
Value in °C room temperature
°C
0 = analog adjustment
1 = digital adjustment on the
controller and via bus
2 = digital adjustment via bus
only
Setting --- = function deacti-
°C
vated
No safety function
Setting --- = function deacti-
°C
vated
17.04.2008
en
55/326