83
Maximum rate of
increase of flow
temperature
84
Excess flow tem-
en
perature mixing
valve / heat ex-
changer
85
Actuator running
time
86
P-band of control
(Xp)
87
Integral action time
of control (Tn)
Block "Boiler"
91
Boiler operating
mode
92
Maximum limitation
of boiler tempera-
ture
93
Minimum limitation of
boiler temperature
94
Switching differen-
tial of boiler
95
Minimum limitation of
Building Technologies
--- °C/h
(--- / 1...600)
°C/h
..............
10 °C
(0...50)
°C
...................
120 s
(30...873)
......................
s
32.0 °C
(1.0...100.0)
°C
...................
120 s
(10...873)
......................
s
0
(0 / 1)
........................
.
95 °C
(25...140)
°C
...................
10 °C
(5...140)
°C
...................
6 °C
(1...20)
°C
...................
4 min
74 319 0618 0 a
Setting --- = function deacti-
vated
(function prevents cracking
noise in piping)
Setpoint boost for precontroller
in interconnected plants
0 = with manual shutdown
(
key)
1 = with automatic shutdown
(OFF when there is no de-
mand for heat)
No safety function
17.04.2008
56/326