en
Technical data
Detection distances of Dräger Flame 2570
Type of fuel
Percentage of base-
line fire value at
respective
detection distance
Gasoline
Jet fuel (JP5)
Kerosene
Diesel fuel
Methane (gas flame)
Liquefied petroleum
gas (LPG, gas flame)
Ethanol 95%
Isopropyl alcohol
(IPA)
Methanol
Polypropylene
Paper
24
Max. distance when
sensitivity level 4
is set
in meters (feet)
100%
90 (300)
70%
62 (205)
70%
62 (205)
70%
62 (205)
70%
62 (205)
70%
62 (205)
60%
55 (185)
60%
55 (185)
55%
48 (160)
55%
48 (160)
38%
34 (115)
Detection distances of Dräger Flame 2500 and Dräger Flame 2700
Type of fuel
Percentage of base-
line fire value at
respective
detection distance
Gasoline
Jet fuel (JP5)
Kerosene
Diesel fuel
Methane (gas flame)
Liquefied petroleum
gas (LPG, gas flame)
Ethanol 95%
Isopropyl alcohol
(IPA)
Methanol
Polypropylene
Paper
Max. distance when
sensitivity level 4
is set
in meters (feet)
100%
65 (215)
70%
45 (150)
70%
45 (150)
70%
45 (150)
70%
45 (150)
70%
45 (150)
60%
40 (135)
60%
40 (135)
55%
35 (115)
55%
35 (115)
38%
25 (82)