Chapter 8 - teChNICaL CharaCterIStICS
8.3 POWER DATA
Power Supply
Power Voltage (R/1L1, S/3L2, T/5L3) (220 to 575) Vac (-15 % to +10 %), or
Frequency
Capacity
Maximum number of starts per hour
(without ventilation)
Maximum number of starts per hour
with optional ventilation Kit
Start cycle
Thyristors (SCRs)
Overvoltage category
8.4 ELECTRONICS AND PROGRAMMING DATA
Power Supply
Control voltage
Connector (A1, A2)
Frequency
Consumption
Control
Method
Inputs
Digitals
Outputs
Relay
Safety
Protections
54
CALL NOW 800-985-6929
http://www.automatedpt.com/
(187 to 632) Vac
(50 to 60) Hz (±10 %), or (45 to 66) Hz
10 (1 every 6 minutes; models from 17 A to 30 A)
3 (1 every 20 minutes; models from 45 A to 200 A)
10 (1 every 6 minutes; models from 255 A to 412 A)
10 (1 every 6 minutes; models from 45 A to 200 A)
3 x In of the SSW-07 during 30 seconds
Reverse voltage with 1600 V maximum peak
III (UL508/EN61010)
(110 to 240) Vac (-15 % to +10 %), models from 17 A to 200 A
(110 to 130) Vac or (208 to 240) Vac (-15 % to +10 %) (models
from 255 A to 412 A)
(50 to 60) Hz (±10 %), or (45 to 66) Hz
15 VA models from 17 A to 200 A
60 VA continuos
800 VA additional during By-pass closing (models from 255 A
to 412 A).
Voltage ramp;
Current limitation.
3 Isolated digital inputs;
Minimum upper level: 93 Vac;
Maximum lower level: 10 Vac;
Maximum voltage: 264 Vac;
Input current: 1.1 mA @ 220 V;
Programmable functions.
2 relays with NO contacts, 240 Vac, 1 A, and programmable
functions.
Overcurrent;
Phase loss;
Inverted phase sequence;
Heatsink overtemperature;
Motor overload;
External fault;
Open By-pass contact;
Closed By-pass contact;
Overcurrent before By-pass;
Stall;
Frequency out of range;
Electronic supply undervoltage.