WEG SSW-07 Manual Del Usuario página 50

Arrancador suave
Ocultar thumbs Ver también para SSW-07:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

CALL NOW 800-985-6929
Protection
Description and
Fault Display
Undervoltage
in the control
supply
E70
(LED Fault)
Flashes twice
(LED Ready)
Off
Internal
By-pass relay
contact Open
E71
(LED Fault)
Flashes 3 times
(LED Ready)
Off
Overcurrent
before the
By-pass
E72
(LED Fault)
Flashes 4 times
(LED Ready)
Off
Frequency out
of tolerance
E75
(LED Fault)
Flashes once
(LED Ready)
Off
Closed By-pass
contact or
shorted SCR's
E77
(Fault LED)
flashes 6 times
(Ready LED) is
off
CALL NOW 800-985-6929
http://www.automatedpt.com/
Chapter 6 - SOLUtION aND trOUBLeShOOtING
Activation Description
Activates when the control
supply voltage is lower than 93
Vac.
When there is a fault with the
internal By-pass relay contacts
at full voltage.
Activates before the closing
of the By-pass if the current is
greater than:
37.5 A for the models up to 30 A;
200 A for the models from
45 to 85 A;
260 A for the model of 130 A;
400 A for the models from
171 and 200 A.
824 for the models from 255 A to
412 A.
When the limit is higher or lower
than the limits of 45 to 66 Hz.
When the SSW-07 does not
detect voltage difference
between the input and output
at the moment the motor is
switched off.
table 6.1 - Faults and possible causes (cont.)
http://www.automatedpt.com/
Probable Causes
Electronics supply lower than the
minimum value.
Electronics power supply with loose
contact.
Electronics power supply fuse blown.
Loose contact in the starting cables
of the Internal By-pass relays.
Defective By-pass relay contacts due
to an overload
The time programmed for the
acceleration ramp is shorter than the
actual acceleration time.
Nominal motor current higher than
the current that can be supported by
the Soft-Starter.
Motor shaft is locked, rotor blocked.
The line frequency is out of range.
When the Soft-Starter + motor are
being supplied by a generator that
is not supporting the full load or the
start of the motor.
Bad contact in the bypass cables.
By-Pass contacts are welded.
Short-circuited thyristor.
Input and output external short-
circuit.
Disconnected motor.
Reset
Power-on.
Reset key.
Auto-reset.
DIx.
Power-on.
Reset key.
Auto-reset.
DIx.
Power-on.
Reset key.
Auto-reset.
DIx.
Power-on.
Reset key.
Auto-reset.
DIx.
Power-on.
Reset key.
DIx.