Chapter 3 - INStaLLatION aND CONNeCtION
3.2.7 Control
and Signal
Connections
Terminal
A1
A2
Terminal
DI1
DI2
DI3
13
14/23
24
22
CALL NOW 800-985-6929
EMI - Electronic Interference
The Soft-Starter SSW-07 is developed to be used in industrial
systems (Class A) according to Standard EN60947-4-2.
It's necessary to have a distance of 0.25 m (10 in) between the
Soft- Starter SSW-07 control cables and motor cables.
Example: PLC wiring, temperature controllers, thermocouple cables, etc.
Grounding of the Motor frame
Always ground the motor frame. The Soft-Starter SSW-07 output
wiring to the motor must be installed separately from the input wiring
as well as from the control and signal wiring.
The control connections (digital inputs and relay outputs) are made
through the terminals (refer to figure 3.9).
Description
Electronics Supply
Grounding
Factory Default
Starts/Stops Motor
Fault reset
Fault reset
Relay 1 output - Operation
Relay common point
Relay 2 output - Full voltage
table 3.9 - Description of the control connector pins
Figure 3.9 - Control terminals of the Soft-Starter SSW-07
NOTE!
It is recommended to use shielded cables for the Dix inputs when
using long cables (above 30 m) in noisy environments. The metallic
shield and A2 must be grounded.
http://www.automatedpt.com/
Specifications
Voltage: 110 to 240 Vac (-15 % to +10 %)
(models from 17 A to 200 A)
110 to 130 Vac or 208 to 240 Vac
(-15 % to 10 %) (models from 255 A
to 412 A).
Only for the 255 to 412 A models
Specifications
3 isolated digital inputs
Voltage: 110 to 240 Vac (-15 % to +10 %)
Current: 2 mA Max.
Contact capacity:
Voltage: 250 Vac
Current: 1 A
http://www.automatedpt.com/
Torque Nm
(in lb)
0.5 (4.5)