General Data - SMA SUNNY TRIPOWER Serie Instrucciones De Instalación

Ocultar thumbs Ver también para SUNNY TRIPOWER Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

SMA Solar Technology America LLC
Maximum utility backfeed current to utility
Limits of accuracy of voltage measurement
Limits of accuracy of frequency measurement
Limits of accuracy of time measurement at nomi-
nal trip time
Output power at +60°C (+140°F)
Maximum power operating ambient tempera-
ture
Power factor at rated power
Displacement power factor, adjustable
Feed-in phases
Phase connection
Overvoltage category in accordance with
UL1741
Efficiency
Maximum efficiency, η
CEC efficiency, η
CEC
* preliminary value

14.2 General Data

Width x height x depth
Weight
Length x width x height of the packaging
Transport weight
Operating temperature range
Storage temperature
Maximum permissible value for relative humid-
ity, non-condensing
Installation Manual
max
STP 24000TL-US-10
2 %
±0.1 Hz
±0.1 %
17000 W
+45°C (+113°F)
1
0
to 0
overexcited
underexcited
3
3
IV
STP 24000TL-US-10
98.5 %
98.0 %
665 mm x 650 mm x 265 mm
(26.18 in x 25.59 in x 10.43 in)
55 kg (121 lb)
780 mm x 380 mm x 790 mm
(30.71 in x 14.96 in x 31.10 in)
61 kg (134.5 lb)
-25°C to +60°C
(-13°F to +140°F)
-40°C to +60°C
(-40°F to +140°F)
100 %
STPTL-US-10-IA-xx-17
14 Technical Data
STP 30000TL-US-10
2 %
±0.1 Hz
±0.1 %
21270 W
+45°C (+113°F)
1
0
to 0
overexcited
underexcited
3
3
IV
STP 30000TL-US-10
98.6 %*
98.0 %*
69
Tabla de contenido
loading