Mitsubishi Electric ecodan PAR-WT50R-E Manual De Instalación Y Configuración página 10

Ocultar thumbs Ver también para ecodan PAR-WT50R-E:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 78
Connect the cable connector to CNRF on the control board. Switch ON SW1-8.
Check the maximum reach of the cable and
install the bracket with screws.
Do not excessively pull the cable when
measuring the maximum reach.
<Notice>
● Do not overtighten the screws.
►The bracket may deform or break.
● When installing the bracket, select an interference-free space.
►Keep the installing area at least 10 cm away from metal or a wall box. If unable to do
so, always place the room wireless remote controllers in locations where the com-
munication test determines that the wireless remote controllers are fully capable of
communication with the wireless receiver.
● Do not install the bracket with screws on the exterior casing of the cylinder unit.
►The internal parts may be damaged, which could result in breakdown of the indoor unit.
● Do not install the bracket where the receiver could be exposed to moisture or
leaked water from piping connections above.
► The wireless receiver subjected to moisture could cause electric shock, fire, or its
breakdown.
When installing the wireless receiver,
observe the following.
● Keep the other electric or electronic
devices (e.g. radio, induction heating
cooker, microwave oven, refrigerator,
and mobile phone or the like) at least 50
cm away from the wireless receiver.
● Place the wireless receiver in an inter-
ference-free area and keep the wireless
receiver away from metal.
9
SW1
CNRF
Tabla de contenido
loading

Este manual también es adecuado para:

Ecodan par-wr51r-e

Tabla de contenido