BEDFORD W191 ELECTRONIC VARIABLE SPEED DRIVE
Fault
Fault Type
Code
E002
Over-current
E006
Over-voltage
DC Bus
E009
Under-voltage
Controller
E010
Overload
E011
Motor Overload
Output Phase
E013
Failure
E014
IGBT Overheat
www.proindecsa.com / [email protected]
W191 Series Intelligent Controller for Water Pump User Manual
Reason
4. bad earth
1. Speed up or slow down too
fast
2. The voltage of the grid is low
3. There are impurities in the
pump
4. Water pump plugging
1. Abnormal input voltage
2. Slow down too fast
3. Large load inertia
4. Instant power outage and then
call the impact
1. Low input voltage
1. Acc. time is too short;
2. Restart the rotating motor;
3. Low input voltage;
4. Load is too heavy
1. Low input voltage;
2. Wrong
setting
parameter;
3. 3.Motor locked-rotor or too
low load mutation;
4. The power of motor is too
small
1. Open-phase occurred at output
side of main circuit
1. Sudden over-current;
2. Input/output side has short
circuit;
3. Cooling fans of controller
blocked or damaged;
4. Ambient temperature is too
high;
Page 20
 Extend
the
deceleration time
 Check the incoming power supply
 Check the water quality and the
inlet water environment
 Check the motor and water pump
 Check input power
 Extend the deceleration time
 Increase the energy consumption
brake assembly
 Avoid restart during shutdown
 Check the grid ' s input power
supply
 Extend Acc. time;
 Avoid restarting the motor until it
stops running completely;
 Check the power supply;
 Select bigger power controller
 Check the power supply;
of
motor
 Set the rated current of motor
properly;
 Check the load, adjust the value of
torque boost;
 Select proper power motor
 Check the wiring, installation and
the power supply
 Refer to measures of over-current;
 Check the wiring;
 Replace cooling fans;
 Decrease
temperature;
 Ask supplier for support
40
Solution
acceleration
and
the
ambient
loading

Este manual también es adecuado para:

Bedford w191-2003