BEDFORD W191 ELECTRONIC VARIABLE SPEED DRIVE
Function
Name
Code
Motor Rated
b00.36
Speed
Motor Rated
b00.37
Voltage
Motor Rated
b00.38
Current
Quick
b00.39
debugging
setting
Alternating
b00.40
time
Alternating
b00.41
Mode
Anti-freezing
b00.42
Frequency
Below Lower
Limit
b00.43
Frequency
Run Selection
Output Phase
Loss
b00.44
Protection
Selection
Setting
b00.45
Password of
b00.00
www.proindecsa.com / [email protected]
W191 Series Intelligent Controller for Water Pump User Manual
Setting
Factory
Range
Default
960~3600
2900rpm
100~250
220V
0.01~
10.00A
13.00
0x 100~
0x100
0x 320
0.00~
8.00h
300.0
0~1
0
10.00~
10.00Hz
b00.26
0~2
1
0~1
1
0-65535
0
Page 13
Description
In order to balance and prolong the pump
service life, the master and auxiliary pumps
alternate acting as the main pump during
running according to the set time, and the unit
is hour.0.00h is not alternating.
0:Alternatingrunning or sleep/wake-up
alternating according to b00.40
1: Only alternating running according to
b00.40
Be valid when b00.43=2.When sleeping, run
with the set frequency in case of freezing. This
value should be lower than b00.26
0: Main pump runs at lower limit frequency
1: Sleep
2: Run at anti-freezing frequency
0: Invalid; 1: Valid
Automatically update to 0 after setting to
single-phase b00.32=1
0 is invalid, non-0 is valid (b00.00 password is
invalid when b00.45 is set to 0 and b00.00
password is valid when b00.45set to non-0)
33