Test Run; Before Test Run - Mitsubishi Electric Mr. SLIM PLA-A BA6 Manual De Instrucciones Para El Instalador

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

6. Electrical work
Function table
Select unit number 00
Mode
Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Filter sign
Fan speed
No. of air outlets
Installed options (high-perform-
ance fi lter)
Up/down vane setting
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.

7. Test run

7.1. Before test run

After completing installation and the wiring and piping of the indoor and out-
door units, check for refrigerant leakage, looseness in the power supply or
control wiring, wrong polarity, and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0 M .
Do not carry out this test on the control wiring (low voltage circuit)
terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 M .
10
Settings
Not available
Available
*1
Indoor unit operating average
Set by indoor unit's remote controller
Wired remote controller's internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
230 V
208 V
Settings
100Hr
2500Hr
No fi lter sign indicator
Silent
Standard
High ceiling
4 directions
3 directions
2 directions
Not supported
Supported
Equipped with vanes (vanes angle setup 3)
Equipped with vanes (vanes angle setup 1)
Equipped with vanes (vanes angle setup 2)
Mode No.
Wired remote controller
(RF thermostat)
01
(101)
02
(–)
03
(103)
04
(104)
Mode No.
Wired remote controller
(RF thermostat)
07
(107)
08
(108)
09
(109)
10
(110)
11
(111)
7.2. Test run
Refer to the installation manual that comes with each remote controller for de-
tails.
7.3. Self-check
Refer to the installation manual that comes with each remote controller for de-
tails.
RF thermostat is not established.
Setting no.
Initial setting
setting
1
2
1
2
3
1
2
3
1
2
Setting no.
Initial setting
setting
1
2
3
1
2
3
1
2
3
1
2
1
2
3