Troubleshooting
9
Troubleshooting
Fault
Leakage at DHW cylinder
Heat-up time too long
DHW temperature too low
Cause
Flange leaking
Pipe connections leaking
Heating water temperature
too low (measure at DHW
cylinder flow, not at heat
generator)
Heating water volume too
low (resulting in a wide
spread, i.e. return tempe-
rature too low)
Internal indirect coil not
vented
Build up of scale on
heating surface
Thermostat switches off
too early
Return temperature too
low (e.g. spread too wide)
Remedy
Tighten bolts to a torque of
20-25 Nm, working
diagonally; replace gasket
Re-seal the connections
Increase temperature
(adjust controller)
Larger pump
Observe back pressure
from parallel heating
circuits
Vent several times with the
pump switched off
Descale heating surface
Readjust thermostat
Larger loading pump