Hayward ENERGY LINE PRO Manual De Instalación E Instrucciones página 49

Ocultar thumbs Ver también para ENERGY LINE PRO:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 68
3. INSTALLATION AND CONNECTION (continued)
3.6 Water flow setting
With the water entry and exit valves being open, adjust the by-pass valve in
order to obtain a difference of 2°C between the inflow and outflow temperature
(see principle diagram § 3.1). You can verify the switch by seeing the entry/
exit temperatures directly on the control panel.
Water inlet temperature
Water outlet temperature
Note: Opening the by-pass valve creates a weaker flow, which leads to an
increase in ∆T.
Closing the by-pass valve creates a stronger flow, which leads to a
decrease in ∆T.
13
loading