5 Installation
5
Installation
5.1
Installation site
5.1.1
Outdoor installation
5.1.2
There must be a ground drain
5.1.3
Ventilation and exhaust
5.1.4
Structure-borne and airborne noise transmission
5.1.5
Reserve space
5.1.6
Fasteners
40 EN
VG 766.2000.055
In order to increase the pump's service life, provide simple weather
protection.
Area around the equipment should have appropriate drainage:
– Size of the swimming pool.
– Circulation flow rate.
Ensure sufficient ventilation and exhaust. The ventilation and
exhaust must ensure the following conditions:
– Prevention of condensation.
– Minimum distance from fan cover to the wall: 50 mm.
– Cooling of the pump motor and other system components, e.g.
switch cabinets and control units.
– Limitation of the ambient temperature to max. 40 °C.
Observe regulations for structural noise protection, e.g. DIN 4109.
Install the pump in a manner which reduces structure-borne and
airborne noise transmission. Vibration-absorbing materials are
suitable bases. Examples:
– Anti-vibration buffers.
– Cork lining.
– Sufficiently hard foam.
Provide enough reserve space to remove the motor unit backward
from the pump in the direction of the motor fan and strainer basket,
please see dimensioned drawing.
Fasten pump by using screws.