3 – Control Panel Features
1
D
2
3
4
•
"NORMAL" LED:
This green light illuminates to indicate that the UPS system is in online (normal) mode. The primary AC input supply is
A
present and within standard operating parameters.
•
"BATTERY" LED:
This amber light illuminates when the UPS system is in battery backup mode, discharging the batteries to provide power
5
B
to connected equipment. An audible alarm will also sound.
•
"BYPASS" LED:
This amber light illuminates when the UPS system is in bypass mode (auto bypass or manual bypass). Battery backup
C
power will not be available to connected equipment while the UPS system is in bypass mode, but connected equipment loads will be
supported by the bypass power source.
6
•
"FAULT" LED:
This red light illuminates when any UPS system or input power fault occurs. Available diagnostic information will be
D
displayed on the LCD screen.
•
LCD Status Screen:
This illuminated LCD status screen displays text and graphics to indicate a wide range of UPS system operating
E
conditions and diagnostic data. Note: The LCD backlight will turn off after 10 minutes of inactivity. Turn on the backlight by momentarily
7
pressing the ON button or one of the scroll buttons.
•
"ESC" (Escape) Button:
F
•
G
Scroll Buttons (
and
buttons are also used for data entry in several screens.
8
•
Enter Button (
): Press this button to select a menu item or confirm a setting change.
H
•
ON Button:
Press and hold this button for 3 seconds to turn the UPS system's inverter ON.
I
•
J
OFF Button:
Press and hold this button for 3 seconds to turn the UPS system's inverter OFF. If the UPS system is in online (normal) mode,
it will switch to auto bypass mode. Note: If the UPS system remains off for an extended period of time, the batteries should be recharged
9
periodically. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every
3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.
•
"EPO" (Emergency Power Off) Button:
K
If the UPS system is in battery backup mode when the EPO button is activated:
10
•
Main output and bypass output are turned off, the alarm sounds, fans shut down after approximately one minute, and control circuitry
remains active.
•
Releasing the EPO button (by pressing it again) turns off the UPS system completely, including the alarm and control circuit. Press the
ON button for 3 seconds to restart the UPS system.
11
If the UPS system is in online (normal) mode when the EPO button is activated:
•
Main output and bypass output are turned off, the alarm sounds, fans and control circuitry remain active.
•
Releasing the EPO button (by pressing it again) turns off the alarm and places the UPS system in auto bypass mode. Press the ON button
for 3 seconds to return the UPS system to online (normal) mode.
12
See
Section 9 – Display and Configuration
13
200803004 93-2793 SU80k manual 4C.indd E6
200803004 93-2793 SU80k manual 4C.indd E6
C
B
A
Press this button to return to the previous page or menu.
): Press these buttons to move the cursor up or down and navigate the control panel menus and screens. These
Press this button to turn the UPS system's output OFF and also disable bypass output.
for detailed information about the control panel's menus and displays.