11 – Specifi cations
1
11-1 UPS System Technical Specifi cations
2
Input
Input Voltage
Voltage Regulation
Harmonic Distortion
3
PFC (Full Load)
Frequency
Frequency Tolerance
Output
Input Voltage
4
Output Frequency
Total Harmonic (Linear Load)
Voltage Regulation
5
Frequency Regulation
Overload
Audible Warning
Battery Backup
6
UPS Abnormal
Display
LED
LCD
7
Interface
Standard
Optional
Others
Parallel Redundancy
EPO
8
SRAM Event Log
Parameter Configuration
Hot Standby Installation
Battery Temperature Compensation
9
Battery Cold-Start
Overall
Efficiency
Transfer Time
10
Temperature
Humidity (non-condensing)
Noise (1 m)
Dimensions (Power Module)
11
Weight (Power Module)
12
11-2 UPS System Floor Loading Table
Model
Weight
13
Floor Loading
200803004 93-2793 SU80k manual 4C.indd E46
200803004 93-2793 SU80k manual 4C.indd E46
Model (Capacity) SU80K (80kVA/64kW)
Static
Dynamic
Interior Oscillator
Synchronized
Normal
ECO
Width
Depth
Height
SU80K
655 kg
1228 kg/m
2
120/208V AC, 3Ø, 4-wire + ground, wye
-25% ~ +20%
< 5% (Full Load)
> 0.99
50 / 60 Hz
45 ~ 65 Hz
120/208V AC, 3Ø, 4-wire + ground, wye
50 / 60 Hz
≤3%
±1%
±7% (10% ~ 90% Linear Load)
±0.05 Hz
±5%
≤125% : 10 minutes; ≤150% : 1 minute
Intermittent
Continuous
UPS Status: Normal • Bypass • Backup • Fault
Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage
UPS abnormal messages with intelligent self-diagnosis.
RS-232, Dry Contact
SNMPWEBCARD
Yes (1+1 for 2 UPS systems of the same type and capacity only.)
Standard (Local and Remote)
500 Records
Yes
Optional
Optional
Standard
92%
96%
0 ms
32° F ~ 104° F (0° C ~ 40° C)
90%
70 dBA
520 mm
1026 mm
1696 mm
655 kg
11-3 Battery Pack Floor Loading Table
BP480V26B
(40 12V batteries;
Model
26AH each)
Weight
470 kg
Floor Loading
1064 kg/m
46
BP480V40C
(40 12V batteries;
40AH each)
700 kg
2
2
1575 kg/m
6/16/2008 1:44:01 PM