Tripp-Lite SU80K Manual Del Propietário página 42

Idiomas disponibles

Idiomas disponibles

10 – Communications
1
10-4 Remote Emergency Power Off (EPO) Circuit Diagram
The Remote Emergency Power Off (EPO) input connection (P1) allows you to connect the UPS system to your facility's EPO circuit. Connecting
2
the UPS system to the EPO circuit enables remote emergency shutdown of the UPS system's output. Connect EPO input to a user-supplied remote
switch, following the circuit diagram below. This contact is normally open.
3
P1
4
10-5 Auxiliary Dry Contact Input Circuit Diagram
5
The auxiliary dry contact input connections (P2) allow the UPS system to receive external signals. These contacts are normally open.
6
P2
7
8
10-6 External Battery Cabinet Temperature Inputs
9
The external battery cabinet temperature input connections (P3, P4, P5, P6) allow the UPS system to receive signals from an optional accessory
that monitors the temperature of external battery cabinets. Call (773) 869-1234 for more information.
10-7 External Battery Status Input
10
The external battery cabinet status input connection (P7) allows the UPS system to receive external battery cabinet status signals through an
optional cable. Pin 1 = +12V; Pin 2 = detection cable connected; Pin 3 = battery cabinet breaker status (signal active= breaker on; signal inactive =
off); Pin 4 = reserved; Pin 5 = reference voltage. Call (773) 869-1234 for more information.
11
12
13
200803004 93-2793 SU80k manual 4C.indd E42
200803004 93-2793 SU80k manual 4C.indd E42
(continued)
42
6/16/2008 1:44:01 PM
6/16/2008 1:44:01 PM
loading