Olimpia splendid Sherpa S3 E Manual De Instalación página 79

Ocultar thumbs Ver también para Sherpa S3 E:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 181
ERROR
MALFUNCTION
CODE
OR PROTECTION
The DC fan failure
Voltage protection
Pressure sensor failure
Inverter module board EE
prom failure
H6 displayed 10 times in 2
hours
Low pressure protection in
cooling Pe<0.6 occurred 3
times in an hour
Low pressure switch protection
FAILURE CAUSE
AND CORRECTIVE ACTION
1. Strong wind or typhoon below toward to the fan, to make the
fan running in the opposite direction. Change the unit direction
or make shelter to avoid typhoon below to the fan.
2. Fan motor is broken, change a new fan motor.
1. Whether the power supply input is in the available range.
2. Power off and power on for several times rapidly in short time.
Remain the unit power off for more than 3 minutes than power
on.
3. The circuit defect part of Main control board is defective.
Replace a new Main PCB.
1. Pressure sensor connector is loosen, reconnect it.
2. Pressure sensor failure. change a new sensor.
1. The EEprom parameter is error, rewrite the EEprom data.
2. EEprom chip part is broken, change a new EEprom chip
part.
3. Inverter module board is broken, change a new PCB.
Refer to H6
Refer to P0
1. System is lack of refrigerant volume. Charge the refrigerant
in right volume.
2.When at heating mode or DHW mode, the outdoor heating
exchanger is dirty or something is block on the surface. Clean
the outdoor heating exchanger or remove the obstruction.
3. The water flow is too low in cooling mode.increase the water
flow.
4. Electrical expansion valve locked or winding connector is
loosen. Tap-tap the valve body and plug in/ plug off the
connector for several times to make sure the valve is working
correctly.
30
loading