Connection To The Smart Control Box; Electrical Connection; Connecting The Wired External Alarm Box; Connection To The Bms - SFA Smart Control Box Manual De Instalación

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 35

4.2.5 Connection to the Smart Control Box

4.2.5.1 Connecting and locking the connector
1
4.2.5.2 Unlocking and disconnecting the connector
4.2.5.3 Location of Connector Connections
Sanifos
Pump 1: Pump 1
Pump 2: Pump 2
OFF: Low level float
ON: High level float
ALARM: Alarm float
Sanicubic
Pump 1: Pump 1
Pump 2: Pump 2
PRESSOSTAT: ON/Alarm level
2
NOTICE
Pulling force on the cables.
Risk of tearing.
 Cut the cables to the correct length.
 Strip cables and wires.
 Never pull or move the cables when they are connected.
 Do not exert any constraints, e.g. by bending the
cable too tightly.

4.3 ELECTRICAL CONNECTION

DANGER
Electrical connection work performed by an unqua-
lified personnel.
Risk of electric shock!
 The electrical connection must be carried out by a
qualified electrician.
 The electrical connection must comply with the stan-
dards in force in the country of installation.
The device's power supply must be connected to ground (class I) and
protected by a high sensitivity differential circuit breaker (30 mA) rat-
ed at:
- 25 A for single-phase Sanicubic 2 VX, Sanifos with 2 single-phase
Sanipump SLD,
- 16 A for all other cases.
The connection must be used exclusively to provide the power to the
Smart Control Box.

4.4 CONNECTING THE WIRED EXTERNAL ALARM BOX

The cable from the external alarm box is already connected to the elec-
tronic board.
• Connect the jack to the bottom of the external alarm box.
Note: The power supply of the external alarm box is done through the
Smart box. If the jack plug is incorrectly inserted, the external alarm
box will signal a power failure (see 6.4.4 Operation).

4.5 CONNECTION TO THE BMS

Option of a remote alarm facility : dry contact (no voltage).
3 BMS are available: a BMS with NO (Normally Opened) contact, a BMS
with NC (Normally Closed) contact and a configurable NO BMS (see
6.3.3 Settings Menu ).
This contact opens (Normally Closed contact)/closes (Normally
Opened contact) as soon as the station is in alarm mode and remains
opened/closed as long as the default has not been corrected.
The terminals can be connected to a BMS (Building Management Sys-
tem) system or to a live system (max. AC 250V / 16A, DC 250V / 17A).
• Use one of the pre-holes on the side of the enclosure.
• Open the hole by tapping firmly with a screwdriver.
• Connect the connection cable directly to the circuit board using the
illustrations below:
Location of BMS
Single-phase version:

Wiring diagrams

Single-phase version:
NO dry contact
NC dry contact
19
EN
Three-phase version:
External alarm
Tabla de contenido
loading

Tabla de contenido