Control Panel; Starting The Chiller; Parameter Settings; Stopping The Chiller - Parker Hyperchill Plus ICEP040 Manual De Uso

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 19
English
4
Control

4.1 Control panel

Fig.1
1
2
1
2
3
I
QS
O
QS Main power switch.
UP button: press to increment the value of a selected
editable parameter.
DOWN button: press to decrement the value of a selected
editable parameter.
esc
ESC button : to exit without saving;
returns to the previous level;
PRESSED FOR 5s. ALARM RESET.
set
SET button : to exit and saving/ confi rm the value;
go to the next level;
enter on Set Menu;
PRESSED FOR 5s. START CHILLER.
!
Alarm ON (led on: red)
H1 alarms are present.
Pump 1
1
hot gas solenoide valve 1
2
hot gas solenoide valve 2
Pump 2
1
antifreeze heater
2
crankcase heater
3
Q.E. heater
ICEP040-060

4.2 Starting the chiller

• Connect the power supply to the machine by turning the main
isolator switch QS to ON.
set
• Press the button "
" to start up.
• Set the desired temperature on the controller. (par. 4.5.1)
Phases Monitor
Er23
If appears on display the alarm "
", during the start up, the user
must verify the wiring of the input terminals of the disconnecting
switch.
4.2.1
Adjustments at commissioning
a) Water temperature setting. See heading 4.5.
b) Regolation of th pump (only for water version)
Verify correct operation of the pump, using the pressure gauge (read
P1 and P0) and checking the pressure limit values (Pmax and Pmin)
indicated on the pump data plate.
P1 = pressure with pump ON
P0 = pressure with pump OFF
Pmin < (P1-P0) < Pmax
- Example n°1.
Conditions:
closed circuit, pressure P0 = 2 bar
pump data plate values: Pmin 1 bar/ Pmax 3 bar
adjust the valve outlet to give a pressure of 3 bar < P1< 5 bar
- Example n°2.
Conditions:
open circuit, pressure P0 = 0 bar
pump data plate values: Pmin 1 bar/ Pmax 3 bar
adjust the valve outlet to give a pressure of 1 bar < P1 < 3 bar
c) Verify correct operation of the pump similarly under normal running
conditions.
Check also that the amperage of the pump is within the limits indi-
cated on the data plate.
d) Switch off the chiller and proceed to top up the hydraulic circuit at
the "SET" temperature.
e) Check that the temperature of the "treated" water does not fall
below 5 °C and that the ambient temperature in which the hydraulic
circuit operates does not fall below 5 °C. If the temperature is too
low, add the appropriate quantity of glycol, as explained under head-
ing 3.3.2.
Y
ATTENTION !: before switching on the chiller pump, close the
water outlet valve (to be installed at client's care).
Always keep the inlet valve (to be installed at client's care) open.
Switching on the pump, slowly open the chiller water outlet valve
and adjust the fl ow rate as described in point 4.2.1.

4.3 Stopping the chiller

When chiller operation is no longer required, turn the chiller off as
follows: press the button "SET" (5 sec.).
Do not turn off the main switch QS to ensure that any antifreeze protec-
tion devices will still receive electrical power

4.4 Parameter settings

General
There are two levels of protection for parameters:
a) Direct (D): with immediate access, User-changeable;
b) Password protected (U): password required for access; Factory-set
parameters.(do not change).
4.4.1
Chiller parameters
PARAMETER
CODE
C-F
Unit of measurement.
Remote on / off enabling
rE
(see para. 4.4.1.1)..
CF30
Unit address *
Baud rate *
CF31
(see para. 4.4.1.2)
CF32
Protocol modbus *
Alarm relay management
rAL
(see para. 4.4.1.3)
SUP
Supervisor on / off enabling *
dEF
Restore default parameters
* Optional parameter
4.4.1.1 Remote On / Off mode
0
Remote On/Off disabled
Remote On/Off enabled together with local On/Off.
1
In case of loss of power, or the main switch is turned off,
then, on return of power the chiller must be restarted locally
2
Remote On/Off only, local On/Off disabled
Note: if you change the baud rate, the chiller must be switched off
and on again.
4.4.1.2 Baud rate (Optional)
1
3
5
2400
9600
38400
2
4
6
4800
19200
57600
4.4.1.3 Alarm relay management
0
Relay normally deactivated, excited by an alarm.
Relay normally excited (also with control OFF), deactivated
1
by an alarm.
Relay normally excited (only with control ON), deactivated by
2
an alarm or with control OFF.
4 / 8
TYPE
DEFAULT
D
0FF
0
D
1
D
3
D
1
D
0
D
OFF
D
OFF
D
7
115200
Tabla de contenido
loading

Tabla de contenido