5. Electrical work
5.4. Types of control cables
1. Wiring transmission cables: Shielding wire CVVS or CPEVS
• Cable diameter: More than 1.25 mm
2
2. M-NET Remote control cables
Kind of remote control cable Shielding wire MVVS
Cable diameter
More than 0.5 to 1.25 mm
When 10 m is exceeded, use cable with the same
Remarks
specifications as transmission line wiring
6. Test run (Fig. 6-1)
BC
CENTRALLY CONTROLLED
ON OFF
CLOCK
CHECK
˚C
STAND BY
ERROR CODE
DEFROST
TEMP.
2
TIMER SET
PAR-20MAA
Fig. 6-1
All manuals and user guides at all-guides.com
2
D
1Hr.
˚C
FILTER
CHECK MODE
E
TEST RUN
FUNCTION
NOT AVAILABLE
A
ON/OFF
5
FILTER
CHECK TEST
1
3
4
3. MA Remote control cables
Kind of remote control cable 2-core cable (unshielded)
Cable diameter
0.3 to 1.25 mm
1 Press [TEST RUN] button twice → displaying [TEST RUN] on the screen.
2 Press [Selecting operation] button. → Check that wind is blowing out.
3 Press [Fan speed adjustment] button. → Check that the wind speed is changed.
4 Press [Up/down airflow selection] button to change wind direction.
5 Press [ON/OFF] button to clear test run. → Test run stops.
A Lighting in operation
B Displaying inspection code
C Displaying remaining test run time
D Displaying indoor unit's liquid pipe temperature
E Displaying test run
Note:
• The 2-hour-set timer is activated to automatically stop test run after two hours.
• The remote controller displays the temperature of the indoor unit's liquid
pipe on the temperature display section during test run.
2
7