Multiple devices, even of different types, can be connected to the STOP
SAFETY EDGE input if appropriately organised:
- NO devices: connect the 8.2 kΩ resistor in parallel to the device;
- NC devices: connect the 8.2 kΩ resistor in series to the device;
- You can connect multiple NC devices "in series" with each other without
quantity limits;
- If there are multiple devices, all must be connected "in cascade" with a single
8.2 kΩ terminal resistance;
- You can also create a combination of NO and NC types, by placing the two
contacts "in parallel". In this case, you need to place a 8.2 kΩ resistance "in
series" with the NC contact; this also makes it possible to put three devices
together: NO, NC and 8.2 KΩ.

3.7 - Connecting a radio receiver

The control unit has an SM connector for connecting an SMXI, SMXIS, OXI,
OXIT or similar radio receiver (optional accessory, not supplied).
To connect the radio receiver, you must disconnect the mains power supply
from the control unit and insert the receiver as shown in Fig. 8.
Table 2 shows the actions performed by the control unit according to the acti-
vated outputs or the commands sent by the radio receiver.
Note - For further information, refer to the instruction manual for the receiver.
TABLE 2
SMXI, SMXIS Receiver in "Mode 1 or 2"
output
description
Output No. 1
Step-by-Step
Output No. 2
Partial open; factory setting: it opens to halfway (this
may be changed during the position acquisition phase
or by using the Oview programmer)
Output No. 3
Open
Output No. 4
Close
OXI, OXIT receiver programmed in "extended Mode 2"
command
description
Command No. 1
Step-by-Step
Command No. 2
Partial open; factory setting: it opens to halfway (this
may be changed during the position acquisition phase
or by using the Oview programmer)
Command No. 3
Open
Command No. 4
Close
Command No. 5
Stop
Command No. 6
Step-by-Step Condominium
Command No. 7
Step-by-Step High priority
Command No. 8
Partial open 2
Command No. 9
Partial open 3
Command No. 10
Open and Lock automation
Command No. 11
Close and Lock automation
Command No. 12
Lock automation
Command No. 13
Release automation
Command No. 14
Timed Courtesy light
Command No. 15
Courtesy light ON/OFF

3.8 - Initial startup and electrical connections test

After supplying power to the control unit, carry out the following checks:
• Verify that the green L2 LED (close to the DIP switches) flashes regularly, with
a frequency of 1 flash per second.
• If the system is equipped with photocells, check that their LEDs flash cor-
rectly (RX); the type of flashing is not significant because that depends on other
factors.
• Ensure that the red SAFETY LED near the keyboard cable connector is per-
manently ON (see Safety LED Diagnostics table, Paragraph 6.2).
If any one of these tests fails to comply with requirements, you must discon-
nect the electrical power from the control unit and check the various electrical
connections made previously.

3.9 - Total deletion of the control unit memory

You can delete all the data stored on the control unit and restore it to its original
state with the default settings.
01.
Set dip switches 1-2-3-
4 to ON = the red and
green leds start flashing
quickly
6 – English
All manuals and user guides at all-guides.com
02.
03.
04.
05.
3.10 - Recognition of the safety devices and the Opening and
After performing the initial startup (paragraph 3.8) and be-
fore setting the gate Opening and Closing positions, you
must have the control unit run the recognition phase of
the connected safety devices on the "STOP Safety Edge"
input.
CAUTION! - During the recognition phase, at least
one safety device must be connected to the control
unit.
01.
02.
03.
This procedure must be repeated if a modification is made to the
devices connected to the "STOP Safety Edge" terminal (for example,
after connecting a new device to the control unit).
After performing the recognition of the safety devices on the automated sys-
tem, the control unit must recognise the gate Opening and Closing positions.
CAUTION! - The recognition procedure of the safety devices and the
gate Opening and Closing positions must be done consecutively,
without interruption. You can not perform the recognition of the safety
devices at one time and the recognition of the positions at another
time.
3.10.1 - Recognition of the Opening and Closing positions with
You can program 2 positions, as follows:
Position
Opening
Closing
Caution! - If the direction of rotation does not correspond to the direc-
tion set (Open button = opening direction), you need to invert the "V"
and "W" connections (phase inversion) in the motor connector (fig. 9).
ON
OFF
Press and hold the
STOP button for 3 sec.
until the green and red
leds remain lit
Release the STOP
button
At this point the control
unit performs a RESET
= the red and green leds
start flashing quickly
Set dip switches 1-2-3-
4 to OFF
Closing positions
Set dip switch 1 to ON =
- Green LED begins to flash
rapidly
- Red LED is OFF
Press and hold the STOP button
until the red led comes on and
remains lit (after about 3 sec.)
Release the STOP button
mechanical limit switch
Meaning
Maximum opening position. When the gate reaches
this position it stops.
Maximum closing position. When the gate reaches this
position it stops.
3"
ON
OFF
ON
OFF
RESET
ON
OFF
OPEN
OPEN
STOP
STOP
CLOSE
CLOSE
ON
OFF
3"
ON
OFF
Tabla de contenido
loading

Tabla de contenido