6.9.1.2
Gas connection
Only certified components must be used for the gas line connections.
A hose is supplied as standard having an inner diameter of 6 mm and an outer diameter of 8 mm, including ¾"G
swivel fittings.
The generator is complete with:
• a double gas valve;
• a gas filter.
It is mandatory to use an EN126-certified large capacity gas filter with filtration level inferior or equal to
50 micron, without pressure stabilizer, because the filter installed as standard upline of the gas valve
has a small surface.
For correct maintenance, the connection to the hot air generator must be implemented using an o-ring
gasket.
Do not put threaded fittings on the gas fitting directly.
The figure shows the diagram to reference for the connection.
The components involved are:
1 main burner;
2 gas solenoid valve in main burner;
3 pressure stabilizer;
4 safety gas solenoid valve;
5 small-section gas filter;
6 vibration dampening joint;
7 large-section gas filter;
8 gas valve;
9 pilot burner;
10 gas solenoid valve in pilot burner.
CGB = components included in hot air generator (unit)
BI = components under the responsibility of the installer
Under no circumstances should the gas circuit be supplied at pressures exceeding 60 mbar.
The risk is that the valve may break.
Translation from original instructions
Packaged Rooftop
60
1
2
3
9
10
Fig. 40 Gas supply to hot air generator
4
5
7
CGB
6
8
BI
We reserve the right to make changes without any prior notice.
UATYA
4P645202-2