Changes to this calibration during installation are legible even when the burner is in
operation by acting on the adjusting screws of the cams.
Tightening the screws increases the angle and positioning of the cams.
Adjusting screws
GAS VALVE ADJUSTMENT
The maximum delivery and the start up delivery must be set.
MAXIMUM DELIVERY ADJUSTMENT
- Assemble a gauge to measure the gas pressure at the burner head.
- Open the gas valve to the maximum.
- While the burner is working, act on the stabilizer until the required delivery is reached
(read the meter): read the pressure value on the
gauge.
- Act on the valve adjustment by turning the valve
towards off until the pressure on the gauge just
hints at decreasing. At this point the maximum
delivery required is set and controlled by both
the stabilizer and the gas valve.
CAMMA II-III (MV1-MV2)
CAMMA IV (1 Stage)
CAMMA V (2 Stage)
UK
Gauge
35