Fault-Finding Chart - Lamborghini Caloreclima EM 9/2-E Manual Para La Instalacion Y El Mantenimento

Quemadores de gas con dos llamas para calderas normales/ presurizadas
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

WARNING:In the event of replace-
ment or assembly/disas-sembly of the
fan, make sure that the latter does not
touch the motor platform as illustrated
in the inclosed diagram.

FAULT-FINDING CHART

DEFECT
The burner does not start-up
The burner starts, the flame
does not form and it therefore
blocks
The burner starts, the flame
forms and it therefore blocks
0,8 - 1,2 mm
CAUSE
No electrical power
Gas does not reach the burner
The gas valves do not open
There is no discharge between
the points of the electrodes
No air pressure switch con-
sent
No or insufficient flame detec-
tion by the control electrode
REMEDY
Control the power supply line fu-
ses. Control the thermostats and
gas pressure switch lines
Check the opening of the shut-off
devices positioned along the sup-
ply piping.
Check valves functioning
Check ignition transformer fun-
ctioning and the positioning of the
electrode points
Check calibration and functioning
of the air pressure switch
Check the positioning of the con-
trol electrode.Control the value of
the ionisation current
M
UK
41
Tabla de contenido
loading

Tabla de contenido