Software Diagnostics - Riello RL 190 TL Instrucciones De Instalación, Uso Y Mantenimiento

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

9.5

Software diagnostics

Reports burner life by means of an optical link with the PC, indicating hours of operation, number and type of lock-outs, serial number
of control box etc.
To view diagnostics, proceed as follows:
– Hold the button down for more than 3 seconds once the red LED (burner lock-out) remains steadily lit.
A yellow light pulses to tell you the operation is done.
Release the button for 1 second and then press again for over 3 seconds until the yellow light pulses again.
Once the button is released, the red LED will flash intermittently with a higher frequency: only now can the optical link be activated.
Once the operations are done, the control box's initial state must be restored using the resetting procedure described above.
Button pressed for
Between 1 and 3 seconds
More than 3 seconds
More than 3 seconds starting from the visual
diagnostics condition
The sequence of pulses issued by the control box identifies the possible types of malfunction, which are listed in the table on pag. 24
SIGNAL
No blink
The burner does not start 1
2 led blinks
After pre-purge and the
safety time, the burner
goes to lock-out and the
flame does not appear
4 led blinks
The burner starts and
then goes into lock-out
20054351
Control box status
Control box reset without viewing visual diagnostics.
Visual diagnostics of lock-out condition: (LED pulses at 1-second intervals).
Software diagnostics by means of optical interface and PC (hours of operation,
malfunctions etc. can be viewed)
FAULT
- No electrical power supply . . . . . . . . . . . . . . . . . . . . . . .
2
- Limit control device TL is open. . . . . . . . . . . . . . . . . . . .
3
- Safety control device TS is open . . . . . . . . . . . . . . . . . .
4
- Control box lock-out . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
- Pump is jammed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
- Erroneous electrical connections . . . . . . . . . . . . . . . . . .
7
- Defective control box . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
- Defective electrical motor . . . . . . . . . . . . . . . . . . . . . . . .
9
- No fuel in tank; water on tank bottom. . . . . . . . . . . . . . .
10 - Inappropriate head and air gate valve adjustments . . . .
11 - Light oil solenoid valves fail to open (1st stage or safety) Check connections; replace coil
12 - 1st stage nozzle clogged, dirty, or deformed . . . . . . . . .
13 - Dirty or poorly adjusted firing electrodes . . . . . . . . . . . .
14 - Grounded electrode due to broken insulation . . . . . . . .
15 - High voltage cable defective or grounded . . . . . . . . . . .
16 - High voltage cable deformed by high temperature. . . . .
17 - Ignition transformer defective. . . . . . . . . . . . . . . . . . . . .
18 - Erroneous valves or transformer electrical connections
19 - Defective control box . . . . . . . . . . . . . . . . . . . . . . . . . . .
20 - Pump unprimed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21 - Pump/motor coupling broken . . . . . . . . . . . . . . . . . . . . .
22 - Pump suction line connected to return line . . . . . . . . . .
23 - Valves up-line from pump closed . . . . . . . . . . . . . . . . . .
24 - Filters dirty: line - pump - nozzle . . . . . . . . . . . . . . . . . .
25 - Defective photoresistor or control box . . . . . . . . . . . . . .
26 - Photoresistor dirty . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27 - 1st stage operation of cylinder is faulty . . . . . . . . . . . . .
28 - Motor protection tripped . . . . . . . . . . . . . . . . . . . . . . . . .
29 - Defective motor command control device . . . . . . . . . . .
30 - 2-phase power supply thermal relay trips. . . . . . . . . . . .
31 - Incorrect motor rotation direction . . . . . . . . . . . . . . . . . .
32 - Photoresistor short-circuit . . . . . . . . . . . . . . . . . . . . . . .
33 - Light is entering or flame is simulated . . . . . . . . . . . . . .
Maintenance
PROBABLE CAUSE
24
GB
SUGGESTED REMEDY
Close all switches - Check fuses
Adjust or replace
Adjust or replace
Reset control box (no sooner than 10 s after the lock-
out)
Replace
Check
Replace
Replace
Top up fuel level or suck up water
Adjust, see pag. 12 and pag. 18
Replace
Adjust or clean
Replace
Replace
Replace and protect
Replace
Check
Replace
Prime pump and see "Pump unprimes"
Replace
Correct connection
Open
Clean
Replace photoresistor or control box
Clean
Change cylinder
Reset thermal cut-out
Replace
Reset thermal cut-out when third phase is re-con-
nected
Change motor electrical connections
Replace photoresistor
Eliminate light or replace control box