Resetting The Control Box And Using Diagnostics; Resetting The Control Box; Visual Diagnostics; Software Diagnostics - Riello RL 190 Instrucciones De Instalación, Uso Y Mantenimiento

Quemadores de gasóleo
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

8.4

Resetting the control box and using diagnostics

The control box features a diagnostics function through which
any causes of malfunctioning are easily identified (indicator: RED
LED).
To use this function, you must wait at least 10 seconds once it
has entered the safety condition (lock-out), and then press the
reset button.
RED LED on
wait at least 10s
The methods that can be used to reset the control box and use
diagnostics are given below.
8.5

Resetting the control box

To reset the control box, proceed as follows:
– Hold the button down for between 1 and 3 seconds.
The burner restarts after a 2-second pause once the button is
8.6

Visual diagnostics

Indicates the type of burner malfunction causing lock-out.
To view diagnostics, proceed as follows:
– Hold the button down for more than 3 seconds once the red
LED (burner lock-out) remains steadily lit.
8.7

Software diagnostics

Reports burner life by means of an optical link with the PC, indi-
cating hours of operation, number and type of lock-outs, serial
number of control box etc.
To view diagnostics, proceed as follows:
– Hold the button down for more than 3 seconds once the red
LED (burner lock-out) remains steadily lit.
A yellow light pulses to tell you the operation is done.
Button pressed for
Between 1 and 3 seconds
More than 3 seconds
More than 3 seconds starting from the visual
diagnostics condition
The sequence of pulses issued by the control box identifies the
possible types of malfunction, which are listed in the table on
page 24.
Burner calibration
The control box generates a sequence of pulses (1 second
apart), which is repeated at constant 3-second intervals.
Once you have seen how many times the light pulses and identi-
fied the possible cause, the system must be reset by holding the
button down for between 1 and 3 seconds.
Press reset
Lock-out
for > 3s
released.
If the burner does not restart, you must make sure the limit
thermostat is closed.
A yellow light pulses to tell you the operation is done.
Release the button once the light pulses. The number of times
it pulses tells you the cause of the malfunction, according to
the coding system indicated in the table on page 24.
Release the button for 1 second and then press again for over
3 seconds until the yellow light pulses again.
Once the button is released, the red LED will flash intermittent-
ly with a higher frequency: only now can the optical link be ac-
tivated.
Once the operations are done, the control box's initial state must
be restored using the resetting procedure described above.
Control box
Control box reset without viewing visual diagnostics.
Visual diagnostics of lock-out condition: (LED pulses at 1-second intervals).
Software diagnostics by means of optical interface and PC (hours of operation,
malfunctions etc. can be viewed)
21
GB
Interval
Pulses
3s
Pulses
6080