mabe MMI09CDBWCCCHI8 Manual Del Propietário página 88

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

88
CAUTIONS
• Provide an individual power circuit specifically for the air condi-
tioner. As for the method of wiring, refer to the circuit diagram
posted on the inside of the access door.
• Confirm that the cable thickness is as specified in the power source
specification.
• Check the wires and make sure that they are all tightly fastened
after cable connection.
• Be sure to install a ground leakage circuit breaker in wet or moist
areas.
cable specifications
Models by capacity
7 000 to 12 000 BTU/h
7 000* to 12 000* BTU/h
14 000 to 18 000 BTU/h
14 000* to 18 000* BTU/h
21 000 to 36 000 BTU/h
21 000* to 30 000* BTU/h
21 000** to 24 000** BTU/h
1.K* Means the power supply of this model comes from indoor unit.
2. K** Indicates indoor power supply unit model with power line
and plug.
3. For models under Tropical Climate condition (T3), the normal cross
section area of Power cord and Power connecting cord is 2.5 mm
2x4.
ATTENTION: The plug must be accessible even after the installation
of the appliance in case there is a need to disconnect it. If this is not
possible, connect appliance to a double-pole switching device with
contact separation of at least 3 mm placed in an accessible position
even after installation.
Power cord
Normal cross
Type
section area
Type
H07RN-F
1,0/1,5 mm² X3
H05RN-F
H07RN-F
1,0/1,5 mm² X3
H07RN-F
H05W-F
1,0/1,5 mm² X3
H07RN-F
H07RN-F
1,5 mm² X3
H05RN-F
H07RN-F
1,5 mm² X3
H07RN-F
H05VV-F
1,5/2,5 mm² X3
H07RN-F
H07RN-F
2,5 mm² X3
H05RN-F
H07RN-F
2,5 mm² X3
H07RN-F
H07RN-F
2,5 mm² X3
H07RN-F
H05VV-F
2,5 mm² X3
H07RN-F
H05VV-F
1,5 mm² X3
H07RN-F
Power connecting cord
Normal cross
section area
0,75 mm² X4
1,0/1,5 mm² X5
1,0/1,5 mm² X4
0,75 mm² X4
1,5 mm² X5
1,5/2,5 mm² X4
0,75 mm² X4
1,0 mm² X4
2,5 mm² X5
2,5 mm² X4
1,5 mm² X4

Capítulos

Tabla de contenido
loading

Tabla de contenido