6. Commissioning, operation / 7. Maintenance and cleaning
Load in Ω
■
Current output (2-wire):
Current output (3-wire):
Voltage output (3-wire):
6.3 Functional check
The output signal must be proportional to the prevailing pressure. If this is not the case, this may indicate a damaged
diaphragm. In this case, see chapter 8 "Faults".
7. Maintenance and cleaning
7.1 Maintenance
This submersible pressure transmitter is maintenance-free.
Repairs must only be carried out by the manufacturer.
7.2 Cleaning
CAUTION!
Prior to cleaning, switch off and disconnect the submersible pressure transmitter from the voltage
■
supply.
Clean the instrument with a moist cloth.
■
Wash or clean the dismounted instrument before returning it, in order to protect persons and the environ-
■
ment from exposure to residual media.
Residual media in dismounted instruments can result in a risk to persons, the environment and
■
equipment. Take sufficient precautionary measures.
Do not use any pointed or hard objects for cleaning, as they may damage the diaphragm of the process
■
connection.
For information on returning the instrument see chapter 9.2 "Return".
WIKA operating instructions submersible pressure transmitter, model LH-10
≤ (power supply - 10 V) / 0.02 A - (cable length in m x 0.14 Ω)
≤ (power supply - 3 V) / 0.02 A - (cable length in m x 0.14 Ω)
> 100 kΩ