Functional Test; Maintenance, Accessories; Trouble Shooting - WIKA C-2 Manual De Instrucciones

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

7. Starting, operation
Specifications
Model C-2
Shock resistance
g
40 (6 ms, 50 repetitions) according to IEC 60068-2-27 (mechanical shock)
20 (20 ... 2000 Hz, 2 h)
Vibration resistance
g
according to IEC 60068-2-6 (vibration under resonance)
Wiring protection
Short-circuit proofness
S+ towards 0V
Reverse polarity protection
UB towards 0V
Overvoltage protection
VDC
max. 36
Weight
kg
Approx. 0.08
{ } Items in curved brackets are optional extras for additional price.
When designing your plant, take into account that the stated values (e.g. burst pressure,
over pressure safety) apply depending on the material, thread and sealing element used.

Functional test

The output signal must be proportional to the pressure. If not, this might point to a
damage of the diaphragm. In that case refer to chapter 9 „Troubleshooting".
Open pressure connections only after the system is without pressure!
Observe the ambient and working conditions outlined in section 7 „Technical
data".
Warning
Please make sure that the pressure transmitter is only used within the over-
load threshold limit at all times!
When touching the pressure transmitter, keep in mind that the surfaces of
the instrument components might get hot during operation.
Caution
10
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio
GB
8. Maintenance, accessories / 9. Trouble shooting

8. Maintenance, accessories

WIKA pressure transmitters require no maintenance.
Have repairs performed by the manufacturer only.
Accessories
For details about the accessories (e. g. connectors), please refer to WIKA's price list, WIKA's
product catalog on CD or or contact our sales department.

9. Trouble shooting

Open pressure connections only after the system is without pressure!
Warning
Take precautions with regard to remaining media in removed pressure trans-
!
mitters. Remaining media in the pressure port may be hazardous or
toxic!
Warning
Remove the pressure transmitter from service and mark it to prevent it from
being used again accidentally, if it becomes damaged or unsafe for opera-
tion.
Have repairs performed by the manufacturer only.
Do not insert any pointed or hard objects into the pressure port for cleaning to prevent
damage to the diaphragm of the pressure connection.
C-2
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio
GB
11
C-2
Tabla de contenido
loading

Tabla de contenido