Functional Test; Adjustment Of Zero Point / Span - WIKA IS-10 Manual De Instrucciones

Transmisor de presión
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

7. Starting, operation
Specifications
Model IS-10 / IS-11
RF-immunity
V/m
BURST
KV
Shock resistance
g
Vibration resistance
g
Wiring protection
Weight
kg
*)
In an oxygen version model IS-11 is not available. In an oxygen version model IS-10 is only available in gauge pressure ranges
≥ 0.25 bar with media temperatures between -4 ... +140 °F / -20 ... +60 °C and using stainless steel or Elgiloy
{ } Items in curved brackets are optional extras for additional price.
When designing your plant, take into account that the stated values (e.g.burst pressure,
over pressure safety) apply depending on the material, thread and sealing element used.

Functional test

The output signal must be proportional to the pressure. If not, this might point to a
damage of the diaphragm. In that case refer to chapter 10 „Troubleshooting".
Open pressure connections only after the system is without pressure!
Observe the ambient and working conditions outlined in section 7
„Technical data.
Warning
Please make sure that the pressure transmitter is only used within the over
load threshold limit at all times!
When touching the pressure transmitter, keep in mind that the surfaces of
the instrument components might get hot during operation.
Caution
14 WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio IS-10, IS-11
10 {30}
4
1000 according to IEC 60068-2-27 (mechanical shock)
20 according to IEC 60068-2-6
(vibration under resonance)
Protected against reverse polarity and short circuiting on the instru-
ment side
Approx. 0.2
®
wetted parts.
GB

8. Adjustment of zero point / span

8. Adjustment of zero point / span (only for pressure transmitter with
clamping nut)
We do not recommend to adjust the span potentiometer. It is used for adjustment ex
factory and should not be adjusted by you unless you have adequate calibration equip-
ment at your disposal (at least three times more accurate than the instrument being
tested).
Make sure wires are not cut or pinche
during disassembly and reassembly of
the connector.
Remove the female connector. Open
the pressure transmitter by detaching
the clamping nut (see Fig. A ). Carefully
remove the male connector from the
case.
Adjust the zero point (Z) (see Fig. B ) by
generating the lower limit of the pressure
range.
Adjust the span (S) by generating the
higher limit of the pressure range.
Check the zero point.
If the zero point is incorrect, repeat
procedure as required.
Reassemble the instrument carefully.
Make sure all sealings and o-rings are
not damaged and correctly installed to
assure the rated moisture ingress protec-
tion.
Recommended recalibration cycle: 1 year
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio IS-10, IS-11
GB
Female
connector
Sealing
Clamping
nut
Male
connector
Sealing
S = Span
Z = Zero
Case with
pressure
A
connection
For further information (+49) 9372/132-295
B
15