Ferroli FORCE W 60 Instrucciones De Uso, Instalación Y Mantenimiento página 258

Ocultar thumbs Ver también para FORCE W 60:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 72
System Type - Parameters Menu
23 parameters are available, indicated by the letter "P." which are not modifiable from Remote Timer Control.
Parameter
P.01
Heating request selection
P.02
Cascade sensor selection
P.03
No function
P.04
3-way valve time
P.05
Activation timer*
P.06
Deactivation timer*
P.07
Activation power*
P.08
Deactivation power*
P.09
Hydraulic separator function
P.10
System filling function
P.11
3-way valve selection
P.12
0-10Vdc Heating OFF voltage (Temperature Control)**
P.13
0-10Vdc Heating ON voltage (Temperature Control)**
P.14
0-10Vdc Max. voltage (Temperature Control)**
P.15
0-10Vdc Min. temperature (Temperature Control)**
P.16
0-10Vdc Max. temperature (Temperature Control)**
P.17
0-10Vdc Heating OFF voltage (Power Control)**
P.18
0-10Vdc Heating ON voltage (Power Control)**
P.19
0-10Vdc Max. power (Power Control)**
P.20
0-10Vdc Min. power (Power Control)**
P.21
0-10Vdc Max. power (Power Control)**
P.22
Enable DHW Slave boiler (Autocascade)
P.23
Continuous comfort Slave boiler (AX5200SQ)
Notes
1. * These parameters are active only when two controllers are connected to a single display ACP01.
2. ** These parameters are active only when the system operates with input 0-10Vdc.
258
Description
cod. 3541V232 - Rev 00 - 08/2021
Range
0 = Normal heating request
1 = Request from remote control with external on-off enabling
2 = 0-10V signal request with temperature control with exter-
nal on-off enabling
3 = 0-10V signal request with external on-off enabling
4 = Control of 2 climatic curves with remote control-room
thermostat and second room thermostat
5 = Control of 2 climatic curves with remote control-room
thermostat and second room thermostat
0 = Disabled
1 = CH + DHW (Heating + DHW)
2 = CH (Heating)
0-1
0 ÷ 255 seconds
0 ÷ 255 minutes
0 ÷ 255 minutes
0 ÷ 100%
0 ÷ 100%
OFF = Disabled, ON = Enabled
OFF = Disabled, ON = Enabled
2/3 = 2 or 3 wires
2 = 2 wires
0.1-10 Vdc
0.1-10 Vdc
0.1-10 Vdc
0 ÷ 100°C
0 ÷ 100°C
0.1-10 Vdc
0.1-10 Vdc
0.1-10 Vdc
0-100%
0-100%
OFF = Disabled, ON = Enabled
OFF = Disabled, ON = Enabled
FORCE W
W 60 W 80 W 99 W 120 W 150
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
5
5
5
5
5
70
70
70
70
70
25
25
25
25
25
OFF OFF OFF OFF
OFF
OFF OFF OFF OFF
OFF
2/3
2/3
2/3
2/3
2/3
2.5
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
3.0
10
10
10
10
10
20
20
20
20
20
90
90
90
90
90
2.5
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
3.0
10
10
10
10
10
0
0
0
0
0
100 100 100
100
100
OFF OFF OFF OFF
OFF
OFF OFF OFF OFF
OFF
EN
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Force w 80Force w 99Force w 120Force w 150

Tabla de contenido