126 D.h.w. temperature
127 D.h.w. charging
128 D.h.w. switching
129 Maximum d.h.w.
130 Setpoint of le-
131 Forced charging
Block "3-position actuator d.h.w."
132 Flow temperature
Building Technologies
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk -
[email protected] 0844 556 1818
0
sensor / d.h.w. ther-
(0...5)
mostat
10 °C
temperature boost
(0...50)
8 °C
differential
(1...20)
60 min
charging time
(--- / 5...250)
--- °C
gionella function
(--- / 20...100)
0
(0 / 1)
10 °C
boost mixing valve /
(0...50)
heat exchanger
74 319 0619 0 a
3 = alternating with space heat-
ing / electric; changeover ac-
cording to all controllers in the
interconnected system
If operating line 54 = 3, this
operating line cannot be
changed. In that case, charging
always takes place via space
heating
0 = 1 sensor
1 = 2 sensors
.........................
2 = 1 thermostat
3 = 2 thermostats
4 = 1 sensor, with solar d.h.w.
heating
5 = 2 sensors, with solar d.h.w.
heating
Plant types x–4 without solar
charging: setting = 0
°C
...................
°C
...................
Setting --- = function deacti-
vated
min
................
Setting --- = function deacti-
vated
°C
...................
0 = none
1 = daily on first release
.........................
°C
...................
17.04.2008
en
55/288