179 Bus power supply
180 Outside tempera-
ture source
en
182 DC 0...10 V heat
demand signal U1
183 DC 0...10 V heat
demand signal U2
Block "Contact H2"
184 Function when ter-
minals H2–M are
linked
Block "External inputs"
185 Effect when connec-
tion terminals H2–M
are linked
186 Demand for heat
when connection
terminals H2–M are
linked
187 Values of voltage
inputs
Building Technologies
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk -
[email protected] 0844 556 1818
A
(0 / A)
.........................
A
A / (00.01...14.16)
.........................
130 °C
(30...130)
°C
...................
130 °C
(30...130)
°C
...................
0
(0 / 1)
.........................
0
(0 / 1)
.........................
70 °C
(0...140)
°C
...................
Display function
74 319 0619 0 a
0 = no bus power supply
through the controller
A = bus power supply through
the controller
No display means: Controller is
autonomous (no data bus pre-
sent)
Setting when supplied via the
data bus:
Segment and device number of
source, or
"A" for automatic identification of
source
Scaling for 10 V
Scaling for 10 V
0 = heat demand signal to heat
source
1 = heat demand signal to heat-
ing circuit
0 = constant
1 = minimum
2
0 = solar radiation in W/m
1 = wind speed in m/s
2 = heat demand at terminal U1
in °C
17.04.2008
62/288