Block "Space heating"
61
62
63
64
65
66
67
68
Building Technologies
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk -
[email protected] 0844 556 1818
Heating limit for
17.0 °C
NORMAL heating
(--.- / −5.0...+25.0)
(ECO day)
Heating limit for
5.0 °C
REDUCED heating
(--.- / −5.0...+25.0)
(ECO night)
Building time con-
20 h
stant
(0...50)
Quick setback
1
(0 / 1)
Room temperature
A
source
(0 / 1 / 2 / 3 / A)
Type of optimization
0
(0 / 1)
Maximum heating
00:00 h
up time
(00:00...42:00)
Maximum optimum
0:00 h
shutdown
(0:00...6:00)
74 319 0619 0 a
Setting --.- = function deacti-
vated
°C
...................
Setting --.- = function deacti-
vated
°C
...................
Light = 10 h, medium = 25 h,
heavy = 50 h
h
......................
0 = no quick setback
1 = quick setback
.........................
0 = no room temperature sen-
sor present
.........................
1 = room unit at terminal A6
2 = room temperature sensor at
terminal B5
3 = mean value of the two units
at terminals A6 and B5
A = automatic selection
0 = optimization with room
model
.........................
1 = optimization with room unit /
room temperature sensor
(setting 0 only allows optimum
start control)
Maximum forward shift for
switching on before occupancy
h
......................
starts
Setting 00:00 = no optimum
start control
Maximum forward shift for
switching off before occupancy
h
......................
ends
Setting 0:00 = no optimum stop
control
17.04.2008
en
49/288