2.4 Constructional requirements of chlorination plants
All chlorine rooms
Fig. 6
Warning sign DIN 4844
– Warning sign according to DIN 4844 part 1 no. 4.2, to be
installed at entrances
Chlorination unit
Acces only for
instructed persons
Fig. 7
Supplementary sign
– Supplementary sign according to DIN 4844 part 1 no. 4.5, to
be installed at entrances
Fig. 8
Mandatory sign
– Mandatory sign according to DIN 4844 part 1 no. 4.3, to be
installed inside the rooms
First aid in the case of
CHLORINE GAS POISONNING
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl lalsdk
HEALTH DANGERS
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
sdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
sdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
FIRST AID
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
k asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
sdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lals
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk
asdajlk llasdf lalsdkfl lasdlfkl lasdflkja
asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj asdlkfjlk lalsdk asdajlk llasdf lalsdkfl lasdlfkl lasdflkjasdlkfjlj jlakjlkjdl alsdfkljkj
Fig. 9
Instruction sheet for first aid
•
Instruction sheet for first aid in case of chlorine gas
intoxications, to be installed inside the rooms
•
Maximum temperature: 50 °C
– recommended temperature: 18 - 20 °C
– recommended minimal temperature: 15 °C
•
Overpressure lines of dosing equipment must not end in the
open air
•
Chlorine rooms must not be dedicated for the permanent stay
of people.
•
Only chlorine containers and the chlorination plant may be
present in the rooms.
Rooms with pressure lines (e. g. storage rooms for chlorine
containers)
•
Flat, even floor
– not below ground level
– not higher than a possible loading ramp
✓
Fig. 10 Regulations for chlorine rooms (1)
✗
Fig. 11 Regulations for chlorine rooms (2)
•
Direct exit to the open air
•
Lockable
– doors must open outwards
– it must be possible to open the doors without a key from
inside the room
•
No connection to other rooms
– separated gastight and fire-resistant from other rooms
•
A maximum of two vent holes of max. 20 cm
•
Water sprinkling system
– for precipitating escaping chlorine gas
– operation must be possiple by hand from outside the
chlorine rooms
– sufficiently dimensioned run-off with air trap
•
Chlorine gas warning system
– with optical and acoustical alarm
– coupled to the water sprinkling system
– coupling must reactivate automatically after having switched
off (e. g. for container exchange)
•
Chlorine gas must not be able to get into lower-lying rooms,
shafts, pits, canals or aspirating holes of ventilation systems.
✗
2
each
9