1.9 Electrical Connections
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
serviced
by
personnel.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards.
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death. Install a transfer
switch in standby power installations to prevent the connection
of standby and other sources of power. Electrical backfeed
into a utility electrical system can cause severe injury or death
to utility personnel working on power lines.
Row Temp. Rating Copper (Cu) Only
1
60_C (140_F)
Use No. * AWG, 60_C wire or
or
use No. * AWG, 75_C wire
75_C (167_F)
2
60_C (140_F)
Use No. * AWG, 60_C wire
3
75_C (167_F)
Use No. *[ AWG, 75_C wire
4
90_C (194_F)
Use No. *[ AWG, 90_C wire
* The wire size for 60_C (140_F) wire is not required to be included in the marking. If included, the wire size is based on ampacities for the
wire given in Table 310-16 of the National Electrical Coder, in ANSI/NFPA 70, and on 115% of the maximum current that the circuit carries
under rated conditions. The National Electrical Coder is a registered trademark of the National Fire Protection Association, Inc.
[ Use the larger of the following conductors: the same size conductor as that used for the temperature test or one selected using the
guidelines in the preceding footnote.
Figure 1-15 Terminal Markings for Various Temperature Ratings and Conductors
The National Electrical Coder is a registered trademark of the National Fire Protection Association, Inc.
TP-6803 1/15
All manuals and user guides at all-guides.com
qualified
electrical
Electrically ground the
Cu/Aluminum (Al) Combinations
Use 60_C wire, either No. * AWG Cu, or No. *
AWG Al or use 75_C wire, either No. * AWG
Cu or No. * AWG Al
Use 60_C wire, either No. * AWG Cu or No. *
AWG Al
Use 75_C wire, either No. *[ AWG Cu or No.
*[ AWG Al
Use 90_C wire, either No. *[ AWG Cu or No.
*[ AWG Al
NOTICE
Canadian installations only. For standby service connect
the output of the generator set to a suitably rated transfer
switch in accordance with Canadian Electrical Code, Part 1.
Have an authorized distributor/dealer or a licensed
electrician make the following electrical connections.
The electrical installation must comply with the National
Electrical Coder (NEC) class 1 wire designation and all
applicable local codes. Canadian installations must
comply with the Canadian Electrical Code (CEC) and
applicable local codes.
AC circuit protection. All AC circuits must include
circuit breaker or fuse protection. The circuit breaker
must be rated for a maximum of 125% of the rated
generator set output current. The circuit breaker must
open all ungrounded connectors. The generator set is
equipped with a factory-installed circuit breaker.
For
customer-supplied
temperature rating in Figure 1-15 based upon the
following criteria:
Select row 1, 2, 3, or 4 if the circuit rating is
D
110 amperes or less or requires #1 AWG (42.4 mm
or smaller conductors.
Select row 3 or 4 if the circuit rating is greater than
D
110 amperes or requires #1 AWG (42.4 mm
larger conductors.
wiring,
select
the
wire
2
) or
Al Only
Use 60_C wire, No. * AWG or
use 75_C wire, No. * AWG
Use 60_C wire, No. * AWG
Use 75_C wire, No.*[ AWG
Use 90_C wire, No.*[ AWG
Section 1 Installation
21
2
)