Assembly layouts

To install the solar collectors refer to the measures indicated in the figure below:
A
at least 1 m right and left of the collector field, for system connection pipes and to allow skilled personnel to intervene if necessary
B
roof lateral protruding part: including the outside wall thickness
C
distance from the ridge cap: at least 1 metre, to avoid damaging the roof fixed parts
D
space below the collectors: at least 1 m to allow skilled personnel to intervene if necessary
E
roof protruding part: including the outside wall thickness
F
vertical distance between the collectors: at least 30 cm, to allow maintenance operations of hydraulic connections
fig. 4 - Installation distances