VLT® Compressor Drive CDS 803
Operating Guide
6 Specifications
6.1 Electrical Data
6.1.1 Electrical Data 3x200–240 V AC
Table 12: 3x200–240 V AC
Typical shaft output [kW]
Typical shaft output [hp]
Enclosure size
Maximum cable size in terminals (mains, compressor) [mm
Output current @ 40 °C (104 °F) ambient temperature
Continuous (3x200–240 V) [A]
Intermittent (3x200–240 V) [A]
Output current @ 50 °C (122 °F) ambient temperature
Continous (3x200–240 V) [A]
Intermittent (3x200–240 V) [A]
Maximum input current
Continuous (3x200–240 V) [A]
Intermittent (3x200–240 V) [A]
Maximum mains fuses, see
1.3.2.2.1 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], best case/typical
Weight enclosure protection IP20 [kg (lb)]
Efficiency [%], best case/typical
Applies to dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
1
typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss
Efficiency measured at nominal current. For energy efficiency class, see
2
ecoSmart
website.
6.1.2 Electrical Data 3x380–480 V AC
Table 13: 3x380–480 V AC
Typical shaft output [kW]
Typical shaft output [hp]
Enclosure size
Maximum cable size in terminals (mains, motor) [mm
(AWG)]
34 | Danfoss A/S © 2021.06
2
(AWG)]
(1)
(2)
2
1.6.6 Conforming
Standards. For part load losses, see Danfoss
P6K0
P7K5
P10K
6.0
7.5
10
8.0
10
15
H3
H3
H4
4 (10)
4 (10)
16 (6)
Specifications
P6K0
P7K5
P10K
6.0
7.5
10
8.0
10
15
H4
H4
H5
16 (6)
16 (6)
16 (6)
22
28
42
24.2
30.8
46.2
19.8
23
33
21.8
25.3
36.3
21
28.3
41
23.1
31.1
45.1
182/204
229/268
369/386
7.9 (17.4)
7.9 (17.4)
9.5 (22.9)
97.3/97.1
98.5/97.1
97.2/97.1
MyDrive® ecoSmart
website.
MyDrive®
P18K
P22K
P30K
18.5
22
30
25
30
40
H5
H5
H6
16 (6)
16 (6)
35 (2)
AQ32174876762701-000301 / 130R0627