Operating instructions
IN3000 Direct
Tab. 6:
Output parame-
ters for the
IN3000 Direct
safety switch
8014173/XT35/2013-10-28 © SICK AG • Industrial Safety Systems • Germany • Subject to change without notice
Product description
3.6
Signal behavior
The safe state is the switched off state (Electrically
isolated state: Logical "0").
If the actuating element is in the enable zone and
there is no sensor error, both output stages are
enabled (logical "1").
The output parameters are compatible with the
parameters for the input in compliance with
EN 61131-2 type 1 or 2:
Logical "1"
≥ 15 V DC
≥ 11 V DC
Logical "0"
5 V DC
≤
If the actuating element is outside the enable zone,
the outputs are switched off (logical "0").
2 ... 15 mA
15 ... 30 mA
Residual current 0.2 mA