Notes For North American Installations; Important - ABB DCS800 Manual Del Usuario

Ocultar thumbs Ver también para DCS800:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Notes For North American Installations

1. EMC conformity is not usually required in North Ame-
rica. In most cases, the section "Notes on EMC" can be
bypassed. In this manual, you will see references to DIN, EN
and VDE standards. These are European standards and,
generally, do not apply to North America. It is, however,
the responsibility of the user to determine which standards
need to be followed.
. If using a DC contactor, you must connect an auxiliary
contact to a digital input of your choice and set para. Main-
ContAck accordingly. Set the following parameters:
MainContAck (10.21)
DO8BitNo (14.16)
MainContCtrlMode (21.16) =
Set these parameters AFTER macros are loaded but BEFORE
the drive is commissioned.
Digital output 8 (DO-8) must be used to turn the DC
contactor on and off.
DC contactor US:
DC contactor US K1.1 is a special designed contactor with x
NO contacts for C1 and D1 connection and 1x NC contact for
connection of Dynamic Brake resistor RB.
The contactor should be controlled by signal 6.03 Bit 10.
The acknowledge can be connected to parameter:
Overview of the Installation and Commissioning Process
Step 1:
Check converter for damage. Contact ABB Technical Support
if damage is found. In North America, call 1-800-435-7365
(1-800-HELP-365)
Step 2:
Select supporting hardware for the converter:
For specific recommendations for fuses, reactors, and
contactors, see the DCS800 hardware manual or technical
catalog.
Circuit breaker or disconnect:
Current rating
= I
= I
Where: I
= nominal DC motor current
dc
Fuses:
AC Line Fuses: To properly protect the converter, semi-
conductor fuses on the incoming AC power line are required
in all cases.
DC Output Fuses: Fuses between the motor and the
converter are required for all regenerative (4-Q) converters.
=
DI-1 (or any input you
choose for the DC cont.
auxiliary contact)
=
10
DCcontact (3)
10.1 MainContAck
10.3 DCBreakAck
* 0.816 * 1.5 (min)
dc
* 0.816 * .50 (max)
dc
3. If using Dynamic Braking, the drive allows you to se-
lect the stopping method under three different situations.
Parameters 1.0, 1.03 and 1.04 select the stopping
method for loss of
the OnOff, run command (StartStop, Jog1, Jog, etc.), and
E-Stop input, respectively.
Each can be set to:
• RampStop
• TorqueLimit
• CoastStop
• DynBraking
In order to command the drive to perform a DB stop, one
or more of these parameters must be set to DynBraking.
Most users will want the drive to ramp stop when OnOff or a
run command (StartStop, Jog1, Jog, etc.) input is cleared,
and dynamically brake when the E-Stop input is cleared. In
that case, use the following settings:
• Off1Mode (1.0)
• StopMode (1.03)
• E StopMode (1.04) = DynBraking
However, any case is allowed and the final decision is left
to the user.
Other parameters control stops during faults.
See:
LocalLossCtrl (30.7)
FaultStopMode (30.30) SpeedFbFltMode (30.36)
If using EMF feedback with dynamic braking, set:
• DynBrakeDly (50.11) = t
Where: t = the time (sec) it normally takes the motor
to stop during dynamic braking
This is to protect the motor and converter if a commutation
fault should occur. NOTE: DC output fuses are the same
type and size as AC line fuses.
Line reactor:
All thyristor-based dc converters cause notching in the AC
line due to motor commutation. A properly sized line reactor
will mitigate the effect on the line. Unless the converter uses
a dedicated isolation transformer, each converter requires
its own line reactor.
AC or DC contactor:
A contactor is required to safely disconnect the motor from
the incoming power when the converter is off. The contactor
can be installed between the line and the converter (an AC
contactor) or between the converter and the motor (a DC
contactor). Do not use both.
IMPORTANT: Other equipment may be necessary de-
pending on application and local codes.
3ADW000191R0500 DCS800 Quick guide edisf e
= RampStop
= RampStop
ComLossCtrl (30.8)
15
Tabla de contenido
loading

Tabla de contenido