Condensation protection (only available for thermostat Blueface on installations with cooling radiant control). Enables to
select the protection level against condensation: Very high, high, medium (by default), low and very low. If necessary,
it can be activated for 1h.
*Note: In Very Low configuration, the humidifier will be automatically activated if the relative humidity level is higher
than 55% in any active zone.
Reset system (only available for master thermostat Blueface). Resets the system and returns to factory settings. To reconfigure
the thermostats, please check Initial configuration).
Information (only for Think thermostats). It provides information about the zone, the system, the devices and the Webserver.
ZONE PARAMETERS
Associated outputs. It displays and allows you to select the control outputs associated with the thermostat.
Thermostat settings. Use this parameter to define the thermostat as Master or Zone.
*Note: It cannot be configured as Master if there is already another Master thermostat.
Use mode. The thermostats can be set in Basic or Advanced mode. They are set in Advanced mode by default. These are the
parameters you can control in basic mode: On/off and set-point temperature.
If you need to reset the thermostat to Advanced mode, access the advanced configuration menu and then activate
the advanced use mode.
Control stages. This parameter is used to configure both cooling and heating stages in a single zone or in all the zones
and your type of installation*.
* In case of selecting Electric in the type of installation, no radiant demand is generated in the CCP and the zone always works
in heating mode, regardless of the operating mode of the system.
Offset. Correction factor for the room temperature of the zones (range: from -2.5ºC to 2.5 ºC in steps of 0.5 ºC). It is in 0ºC
by default.
Reset thermostat. It resets the thermostat and returns it to factory values.
PRODUCCTION PARAMETERS
The configuration parameters of the Production control board (AZX6CCPWSCC) settings are only available in the master
Blueface thermostat of the system nº1.
Operation logic. It allows to configure the operation logic for the control relays of the production control board:
-
Aerothermal unit (Default preset)
-
2 pipes
-
4 pipes
-
RadianT (Recommended for RadianT365 systems)
Activation delay. It allows to set a delay time in the power on of the production unit, configurable in minutes, from 0 to
7. (Default preset to 3 minuts).
LWT temperatures. (Only available in installations with AZX6GAW XXX control gateways) It allows to set the LWT
temperaturas for the heatting and cooling modes of the aerothermal unit. Selectable values depends on each
particular aerothermal unit. Default presets are:
-
Air in cooling mode: 10 ˚C
-
Radiant in cooling mode: 18 ˚C
-
Air in heating mode: 50 ˚C
-
Radiant in heating mode: 35 ˚C