Assembly And Connection Evaluation; Initial Configuration; Airzone Blueface And Think Thermostats; Important - Airzone RADIANT365 Manual De Instrucciones

Ocultar thumbs Ver también para RADIANT365:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1

ASSEMBLY AND CONNECTION EVALUATION

Check the following aspects:
-
The state of the LEDs of the main control board and the rest of control elements. Check the self-diagnose section of
the data sheet of the elements.
ES
-
If all the thermostats are powered.
EN
Important: In the main control board, to verify the correct performance, check D3, D11 and D19 LEDs.
FR
IT
PT
DE

INITIAL CONFIGURATION

AIRZONE BLUEFACE AND THINK THERMOSTATS

Important: Once you start the process, it cannot be interrupted. You will be able to modify the desired parameters later.
Language/Country
Select your language and country. These are the available languages: Spanish, English, French, Italian, Portuguese and German.
To associate a wireless Think thermostat, start the radio channel search:
Setting wireless device
-
Open the radio channel. To do that, press on SW1. The LED D11 will remain solid red. Once
open, you have 15 minutes to make the association. If that period of time expires, start
the process over again. Remember not to open more than one module at the same time,
it may alter the process. You can also open the channel association radio through the
Blueface and Think (see section System parameters).
IMPORTANT: not to open more than one radio channel at the same time, it may alter the process.
-
Start the radio channel search, to do so, press Airzone to start the search.
-
The controller will display the different wireless zone modules found, with the signal level of each one of them. Select
the wanted module and press "Check", the selected module will begin to "beep" to be identified. Verify the range is
correct (30% minimum) and confirm.
Zone address
Select the zone associated to the thermostat. Each zone corresponds to a radiant element relay output (AZRA6CM1VALC).
Associated outputs
If necessary, the system allows you to associate more than one control output to a zone. It is possible to control multiple outputs
from the same thermostat.
24
Main control board activity
D3
D11
Main control board power
D19
Association channel: active
Meaning
Blinking
Solid
Solid
Green
Red
Red
loading

Este manual también es adecuado para:

Azra6radiantAzra6cm1valcAzx6ccpAzx6ccpwscc