Airzone RADIANT365 Manual De Instrucciones página 24

Ocultar thumbs Ver también para RADIANT365:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1
Connect the Airzone connection bus between the RadianT main control board and the thermostats. Use (2x0,5 + 2x0,22
mm
2
Airzone wire. In wireless thermostat, please check that the battery is inserted.
Note: To connect more than 4 Blueface, it is necessary an external power supply unit (AZX6POWER). These values can be altered
depending on the separation distance among them.
You can find the instructions on how to connect and configure other peripherals on their data sheets.
Power supply the Control Module of Radiant Elements (AZRA6CM1VALC) and all the elements which need external power
supply. Use (3x1,5 mm
) wire.
2
Important: According to the current local and national regulations, it is mandatory to add a switch (or other
element to disconnect the system) to the external supply wiring so that a constant separation between poles is
guaranteed. The system will restart automatically if the supply is eventually turned off. Use an independent
circuit from the controlled system for the power supply.
Important: For elements externally powered at 110/230 Vac, for their communications, it is only necessary to connect the poles "A","B"
and "Shield" of the bus.
Note: For the proper functioning of this main control board, all installation main control boards must be addressed and associated
(See Advanced settings section).
Configure the AZRA6CM1VALC module according to your installation. To do this you must leave the LED that
corresponds to your installation on:
Configuratión 1
R1
Pump On/Off
Heating mode norm.open
R2
Cooling mode norm.closed
Configuration 2
Pump On/Off
Heating mode norm.closed
Cooling mode norm.open
Configuration 3
Cooling demand
Heating demand