Hysteresis Configuration. Defines the temperature differential between the room temperature and the set-point
temperature required to start applying the Algorithm RadianT. This algorithm prevents overheating in underfloor air
conditioning installations. If your installation has radiators, set this value to 0ºC. (By default 2ºC)
·
Type of opening. Use this parameter to configure the type of opening of the damper output. (By default All/Nothing).
ES
*Note: If you change this parameter, all the dampers of the installation will be affected. It is not recommended for RINT and
RIC intelligent grilles.
EN
·
Relay settings. Use this parameter to change the operation logic of the CMV/Boiler of the system main control board.
(By default CMV)
FR
·
Return temperature (only available for installations with AZX6SONDPROTEC). Defines the cut-off temperatures of the
system for both heating (32ºC, 34ºC and 36ºC) and cooling mode (6ºC, 8ºC and 10ºC) in order to protect the AC unit. It
is set by default in 34ºC in heating mode and 8ºC in cooling mode.
IT
·
Q-Adapt (only for Think thermostats).
PT
In direct expansion units. Select the control algorithm that best fits your installation. These are the available
-
options:
DE
-
Maximum: the system operates at maximum speed, irrespective of the number of zones.
-
Power: the speed of the system is higher than in standard mode to increase the flow.
-
Standard (by default): the system automatically regulates the speed based on the number of zones.
-
Silence: the speed of the system is lower than in standard mode to reduce the noise.
-
Minimum: the system operates at minimum speed, irrespective of the number of zones.
In 0-10 V Fancoil units. Allows to control the minimum (1.5 V by default) and maximum (10 V by default) working
-
fan voltage of the controlled unit, in steps of 0.1 V. The minimum voltage corresponds with the desired lowest
speed for the unit and the maximum voltage corresponds with the highest speed. The medium speed
corresponds with the mid point between both of them.
·
Radio channel. It activates/deactivates the wireless association module of the system.
·
Info (only for Think thermostats). It provides information about the zone, the system, the devices and the Webserver.
ZONE PARAMETERS
·
Associated outputs. It displays and allows you to select the control outputs associated with the thermostat.
·
Thermostat settings. Use this parameter to define the thermostat as Master or Zone.
*Note: It cannot be configured as Master if there is already another Master thermostat.
·
Use mode. The thermostats can be set in Basic or Advanced mode. They are set in Advanced mode by default. These
are the parameters you can control in basic mode: On/off, set-point temperature and fan speed.
If you need to reset the thermostat to Advanced mode, access the advanced configuration menu and then activate
the advanced use mode.
·
Control stages. This parameter is used to configure both cooling and heating stages in a single zone or in all the
zones. These are the features to be configured:
-
Air: It activates the heating/cooling air in the zone.
-
Radiant (only in heating stages): It activates the radiant heating in the zone.
-
Combined (only in heating stages): It activates both air and radiant heating in the zone selected and allows the
user to select the desired heating stage that in the zone: Air, Radiant or Combined. The zone will start using the
heating air stage. Once the room temperature reaches the differential pre-established (see parameter Hysteresis
Configuration), the zone will activate the radiant stage.
-
Off: It deactivates the cooling/heating stage in the zone.
32