EN: Installation instructions

Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
CEN/TS 54-14 standard and local regulations.
To install a detector
Caution: Always recalibrate optical smoke detectors before
first-time installation.
1.
Insert the detector head into the mounting base and rotate
it clockwise until it clicks into place (Figure 1).
2.
The detector may be locked into the mounting base if
required. To do this, remove the locking tab before
installation (Figure 2).
3.
After installation, ensure that the detector communicates
with the control panel. If the detector does not
communicate with the control panel, check that duplicate
addresses have not been assigned.
4.
Always test detectors after installation.
To remove a locked detector
1.
Insert a small screwdriver into the locking tab slot
(Figure 3).
2.
Press and rotate the detector anticlockwise.
Addressing
Each device requires a numeric address between 1 and 125
for identification purposes. This is assigned at the fire panel or
using a PG700 portable address programmer.
Maintenance
Basic maintenance is reduced to a yearly inspection. Do not
modify internal wiring or circuitry.
To replace the optical chamber (KL731A only)
1.
Remove the detector head from the mounting base.
2.
Remove the detector cover by pressing the catch with a
screwdriver, turning and lifting (Figure 4).
3.
Remove the existing optical chamber and insert the
replacement optical chamber (Figures 5 and 6).
4.
Replace the detector cover and install detector head into
the mounting base.
To clean the optical chamber follow the above instructions for
removal and use compressed air to clear the dust.
Caution: The detector must be recalibrated after cleaning or
replacement of the optical chamber.
Specifications
KL710A
Operating voltage
22 to 38 VDC 22 to 38 VDC
Current
Standby (38V)
250 µA
Alarm
< 11 mA
Pre-alarm indication
Flashing LED Flashing LED
2 / 12
KL731A
KL735A
22 to 38 VDC
250 µA
350 µA
< 11 mA
< 5 mA
Flashing LED
KL710A
Alarm indication
Constant LED Constant LED Constant LED
Coverage
60 to 80 m2
IP rating
IP42
Compatible mounting
KZ700,
base
KZ705,
KZ705D
Temperature:
Operation
-10 to +60ºC
Storage
-10 to +70ºC
Relative humidity
10 to 95%
(noncondensing)
Colour
White
Dimensions (Ø × H )
99 × 45 mm
Weight
75 g
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information refer to the product Declaration of Performance.
Certification
Certification body
1134
Declaration of
360-4222-
Performance number
0399
Year of first CE marking
05
Product Identification
KL710A
Intended use
See DoP point 3
Essential characteristics
See DoP point 9
Manufacturer
Gulf Security Technology Co.,Ltd
80, Changjiang East Road,
QETDZ, Qinhuangdao,
Hebei Province, China 066004
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Contact information
For contact information see our Web site:
www.utcfssecurityproducts.eu.
ES: Instrucciones de instalación
Instalación
Precaución:
Para información sobre el diseño, instalación,
uso y mantenimiento del sistema, aconsejamos seguir la
norma CEN/TS 54-14 y normas locales.
Para instalar el detector
Atención: Siempre recalibre los detectores ópticos antes de
su primera instalación.
KL731A
KL735A
60 to 80 m2
60 to 80 m2
IP42
IP42
KZ700,
KZ700, KZ705,
KZ705,
KZ705D
KZ705D,
KZ705R
-10 to +60ºC
-10 to +60ºC
-10 to +70ºC
-10 to +70ºC
10 to 95%
10 to 95%
White/Black
White
99 × 45 mm
99 × 51 mm
107 g
109 g
360-4222-
360-4222-
0199
0499
05
06
KL731A
KL735A
P/N 55370159 • REV 03 • ISS 16SEP13