KL710A, KL731A, and KL735A Addressable
Point Detectors Installation Sheet
EN ES FR
IT
NL PL PT TR
1
3
EN: Installation instructions
Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
CEN/TS 54-14 standard and local regulations.
To install a detector
Caution: Always recalibrate optical smoke detectors before
first-time installation.
1.
Insert the detector head into the mounting base and rotate
it clockwise until it clicks into place (Figure 1).
© 2015 UTC Fire & Security. All rights reserved.
2
2.
The detector may be locked into the mounting base if
required. To do this, remove the locking tab before
installation (Figure 2).
3.
After installation, ensure that the detector communicates
with the control panel. If the detector does not
communicate with the control panel, check that duplicate
addresses have not been assigned.
4.
Always test detectors after installation.
To remove a locked detector
1.
Insert a small screwdriver into the locking tab slot
(Figure 3).
2.
Press and rotate the detector anticlockwise.
1 / 8
P/N 10-4221-501-KL7A-01 • ISS 30MAR15