en
|
Description
WARNING
Explosion hazard!
A damaged flame path could lead to an explosion. Opening the flame detector
in an explosive atmosphere may cause an explosion.
► Do not open the flame detector in presence of an explosive atmosphere.
► Ensure that the flame path of the flame detector is not damaged during
installation.
CAUTION
Risk of damage to the device!
Incorrect disassembly of the flame detector may damage the device.
► Only appropriately trained service personnel may open the enclosure.
2.2.5
Status indicator
The status of the flame detector is indicated by the colour of a status LED
located below the lens:
LED
Steady OFF
Steady Green
Flashing Green
Steady Yellow
Red
One yellow flash at start up
Two yellow flashes at start up
Three yellow flashes at start up
8
Status
No power/Major internal fault
Healthy
24 V/0 Vdc polarity reversed
Fault
Alarm
Set to low sensitivity (15 m)
Set to standard sensitivity (30 m)
Set to high sensitivity (60 m)
2.3
Intended use
The flame detector is designed for use in areas that may contain a potentially
explosive atmosphere (see "Approvals", page 8).
It is used to monitor an area and trigger the necessary control actions upon the
detection of fire or flame within its field of view.
2.4
Limitations on use
–
The flame detector is not approved for use in oxygen-enriched
atmospheres.
–
As the flame detector responds to flame, it cannot be used in locations
where flare stacks and other open flames are within its field of view without
triggering false alarms.
–
The flame detector responds to CO
cannot detect non-hydrocarbon fires such as those using pure hydrogen,
and sulphur as fuel.
–
The flame detector may be obscured by extremely dense fog, smoke or
other airborne particulates.
–
Arc welding should not take place within 10 m of the flame detector when
using the highest sensitivity setting.
2.5
Approvals
For information - certificate numbers may change.
Authority/
Parameter
Standard
Hazardous area certifica-
ATEX
tion
Hazardous area certifica-
NEC 505
tion
Hazardous area certifica-
NEC 500
tion
Instructions for use
emissions of a flame; therefore, it
2
Approval
Certificate
II 2 G Ex db IIC T4 Gb
FM21ATEX0012X
Class 1,
Zone 1 AEx db IIC T4 Type
4X
Class 1, Div. 1, Groups B,
C, D T4 Type 4X
|
Flame 1500